TITLE 14 HOUSING AND CONSTRUCTION
CHAPTER 8 PLUMBING
CODES
PART 4 2024
NEW MEXICO MEDICAL GAS CODE
14.8.4.1 ISSUING AGENCY. The Construction Industries Division (CID) of the Regulation and Licensing Department.
[14.8.4.1 NMAC – N, 14.8.4.1 NMAC, 08/01/2026]
14.8.4.2 SCOPE. This rule applies to all contracting work performed in New Mexico on or after August 1, 2026, that is subject to the jurisdiction of CID, unless performed pursuant to a permit for which an application was received by CID before that date.
[14.8.4.2 NMAC – N, 14.8.4.2 NMAC, 08/01/2026]
14.8.4.3 STATUTORY AUTHORITY. Section 60-13-9, 60-13-44, 60-13-45, 60-13-46, and 60-13-47 NMSA 1978.
[14.8.4.3 NMAC - N, 14.8.4.3 NMAC, 08/01/2026]
14.8.4.4 DURATION. Permanent.
[14.6.4.4 NMAC - N,
14.8.4.4 NMAC, 08/01/2026]
14.8.4.5 EFFECTIVE DATE. August 1, 2026, unless a later date is cited at the end of a section.
[14.8.4.5 NMAC - N, 14.8.4.5 NMAC, 08/01/2026]
14.8.4.6 OBJECTIVE. The purpose of this rule is to establish minimum standards for the installation, alteration, repair, relocation, replacements, addition to, use, testing, and maintenance of all medical gas and vacuum piping systems in New Mexico.
[14.8.4.6 NMAC - N, 14.8.4.6 NMAC, 08/01/2026]
14.8.4.7 DEFINITIONS. See 14.5.1
NMAC and Chapter 3 of the 2024 NFPA 99 Health Care Facilities Code.
[14.8.4.7 NMAC – N,
14.8.4.7 NMAC, 08/01/2026]
14.8.4.8 ADOPTION
OF THE 2024 NFPA (NATIONAL FIRE PROTECTION ASSOCIATION) 99 HEALTH CARE FACILITIES
CODE:
A. This rule adopts by reference the
2024 NFPA 99 Health Care Facilities Code and all annexes (as explanatory
material), as amended by this rule.
B. In this rule, each provision is numbered to
correspond with the numbering of the 2024 NFPA 99.
C. This rule shall apply in conjunction with the
provisions of all applicable New Mexico construction codes, laws, and
standards.
[14.8.4.8 NMAC - N, 14.8.4.8 NMAC, 08/01/2026]
14.8.4.9 CHAPTER
1 ADMINISTRATION: See this chapter of the NFPA 99 except as provided below.
A. Section 1.1 Scope.
See this section of the NFPA except as provided below.
(1) Section 1.1.1 Delete this
section of the NFPA 99 and see 14.8.4.2 NMAC.
(2) Section 1.1.4 Electrical systems. Delete this section of the NFPA 99 and see
14.10.4
NMAC.
(3) Section 1.1.5 Information
Technology and Communication Systems.
Delete this
section of the NFPA
99.
(4) Section 1.1.6 Plumbing. Delete this section of the NFPA 99 and see
14.8.2 NMAC.
(5) Section 1.1.7 HVAC systems. Delete this section of the NFPA 99 and see
14.9.2
NMAC.
(6) Section 1.1.8 Electrical equipment. Delete this section of the NFPA 99 and see
14.10.4
NMAC.
(7) Section 1.1.9 Gas equipment. Delete this section of the NFPA 99.
(8) Section 1.1.10 Emergency
management. Delete this section of
the NFPA 99.
(9) Section 1.1.11 Security management. Delete this section of the NFPA 99.
(10) Section 1.1.14 Features of fire
protection. Delete this section of
the NFPA 99 and see 10.25.2 NMAC.
B. Section 1.2 Purpose. Delete this section of the NFPA 99 and see
14.8.4.6 NMAC.
C. Section 1.3 Application. See this section of the NFPA 99 except as
provided below.
(1) Section 1.3.1.2. See this section of the NFPA except add the
following to the end of the section: All medical gas and vacuum piping systems
shall be permitted and inspected through the division or local AHJ that has
certified medical gas inspectors in their employ as outlined in 14.6.5 NMAC.
(2) Section 1.3.3 Policies. Delete this section of the NFPA 99.
D. Section 1.4 Equivalency. Delete this section of the NFPA 99 and see
14.5.1 NMAC.
[14.8.4.9 NMAC - N,
14.8.4.9 NMAC, 08/01/2026]
14.8.4.10 CHAPTER
2 REFERENCED PUBLICATIONS: See this chapter of the NFPA 99.
[14.8.4.10 NMAC - N,
14.8.4.10 NMAC, 08/01/2026]
14.8.4.11 CHAPTER
3 DEFINITIONS: See this chapter of the NFPA 99 except as provided below.
A. Section 3.2.2 Authority Having Jurisdiction (AHJ). Delete this definition from the NFPA 99 and
substitute with the following: The authority having jurisdiction is the CID and
the mechanical-plumbing trade bureau chief for adoption, enactment,
interpretation and enforcement of the state adopted medical gas code as the
minimum requirement for the state of New Mexico.
B. Section 3.2.5 Listed. See this definition from the NFPA 99 and add
the following provision at the end of the definition: A manufacturer may select
an independent certification organization of its choice to certify its
products, provided that the certification organization has been accredited by
the American national standards institute (ANSI), or another certification organization
that CID has approved in writing.
C. Section 3.3.15 Bathroom. Delete this definition from the NFPA 99 and
see 14.8.2 NMAC.
D. Section 3.3.16 Battery-Powered Lighting Units. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
E. Section 3.3.18 Branch Circuit. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
F. Section 3.3.23 Clinical IT Network. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
G. Section 3.3.30 Critical Branch. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
H. Section 3.3.34 Debrief. Delete this definition from the NFPA 99.
I. Section 3.3.48 Electrical Maintenance Program (MEP). Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
J. Section 3.3.49 Electrode. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
K. Section 3.3.52 Equipment Branch. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
L. Section 3.3.53 Equipment Grounding Bus. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
M. Section 3.3.54 Essential Electrical System. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
N. Section 3.3.57 Exposed Conductive Surfaces. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
O. Section 3.3.59 Fault Current. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
P. Section 3.3.60 Feeder. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
Q. Section 3.3.71 Ground-Fault Circuit Interrupter. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
R. Section 3.3.72 Grounding. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
S. Section 3.3.73 Grounding System. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
T. Section 3.3.74 Hazard Current. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
U. Section 3.3.87 Immediate Restoration of Service. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
V. Section 3.3.88 Impedance. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
W. Section 3.3.102 Line Isolation Monitor. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
X. Section 3.3.127 Nonessential Electrical Loads. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
Y. Section 3.3.133 Opportunity for Improvement. Delete this definition from the NFPA 99.
Z. Section 3.3.144 Patient Care-Related Electrical
Equipment. Delete this definition
from the NFPA 99 and see 14.10.4 NMAC.
AA. Section 3.3.147 Patient Equipment Grounding Point. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
BB. Section 3.3.148 Patient Lead. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
CC. Section 3.3.153 Plug (Attachment Plug, Cap). Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
DD. Section 3.3.155 Power Sources. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
EE. Section 3.3.163 Reactance. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
FF. Section 3.3.164 Receptacle. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
GG. Section 3.3.165 Reference Grounding Point. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
HH. Section 3.3.166 Relocatable Power Tap (RPT). Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
II. Section 3.3.171 Selected Receptacles. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
JJ. Section 3.3.187 Touch Current. Delete this definition from the NFPA 99 and
see 14.10.4 NMAC.
KK. Section 3.3.194 Waste Water. Delete this definition from the NFPA and see
14.8.2 NMAC.
LL. Section 3.4 BICSI Definitions. Delete this section from the NFPA 99 and see
14.10.4 NMAC.
[14.8.4.11 NMAC - N,
14.8.4.11 NMAC, 08/01/2026]
14.8.4.12 CHAPTER
4 FUNDAMENTALS: See this chapter of the NFPA 99.
[14.8.4.12 NMAC - N, 14.8.4.12 NMAC, 08/01/2026]
14.8.4.13 CHAPTER
5 GAS AND VACUUM SYSTEMS: See this chapter of the NFPA 99 except as
provided below.
A. Section 5.1 Category 1 Piped Gas and Vacuum Systems. See this section of the NFPA 99 except as
provided below.
(1) Section 5.1.3 Category 1 Sources. See this section of the NFPA except as
provided below. Section 5.1.3.3.2
Design and construction. See this
section of the NFPA 99 except as provided below.
(a) Section 5.1.3.3.2.2
See this section of the NFPA 99 except delete subsection (7)
and substitute with
the following: The location shall comply with 14.10.4 NMAC for ordinary
locations.
(b) Section 5.1.3.3.2.2 See this
section of the NFPA 99 except delete subsection (11) and substitute with the
following: The location shall be supplied with electrical power compliant with
the requirements set forth in 14.10.4 NMAC.
(c) Section 5.1.3.3.2.3 See this
section of the NFPA 99 except delete subsection (3) and substitute with the
following: They shall comply with 14.10.4 NMAC.
(d) Section 5.1.3.3.2.3 See this
section of the NFPA 99 except delete subsection (5) and substitute with the
following: They shall be supplied with electrical power compliant with the
requirements set forth in 14.10.4 NMAC.
(e) Section 5.1.3.3.3 Ventilation. See this section of the NFPA 99 except as
provided below. Table 5.1.3.3.2.5
Storage quantities for medical gas and cryogenic fluid central supply systems
in health care facilities. See this
table of the NFPA 99 except delete footnote (c) and substitute with the
following: Indoor structure constructed in accordance with 5.1.3.3.2,
ventilated in accordance with 9.3.6, and provided with an approved, automatic
sprinkler system in accordance with 14.7.2 and 10.25.2 NMAC.
(f) Section 5.1.3.6.3 Medical air compressor supply
systems. See this section of the
NFPA 99 except as provided below. Section
5.1.3.6.3.10 Electrical power and control.
See this section of
the NFPA 99 except as
provided below. Delete subsection (E)
and substitute with the following: Electrical
installation and
wiring shall conform to the requirements of 14.10.4 NMAC. Delete subsection (F) and substitute with the
following: Emergency electrical service for the compressors shall conform to
the requirements of 14.10.4 NMAC.
(g) Section 5.1.3.7.6 Electrical power and control. See this section of the NFPA 99 except as
provided below.
(i) Delete
subsection (E) and substitute with the following: Electrical
installation and
wiring shall conform to the requirements of 14.10.4 NMAC.
(ii) Delete subsection (F) and substitute
with the following: Emergency
electrical service
for the pumps shall conform to the requirements of 14.10.4 NMAC.
(h) Section 5.1.3.8.4 Electrical power and control. See this section of the NFPA 99 except as
provided below.
(i) Section
5.1.3.8.4.5 Delete this section of the NFPA 99 and substitute with the
following: Electrical installation and wiring shall conform to the requirements
of 14.10.4 NMAC.
(ii) Section 5.1.3.8.4.6 Delete this
section of the NFPA 99 and substitute with the following: Emergency electrical
service for the producers shall conform to the requirements of 14.10.4 NMAC.
(i) Section
5.1.3.10.2 Cryogenic fluid central supply systems installation.
Delete this section
of the NFPA 99 except Section 5.1.3.10.12 Alarms.
(2) Section 5.1.9 Category I warning
systems. See this section of the
NFPA 99 except as provided below.
(a) Section 5.1.9.1 General. See this section of the NFPA 99 except as
provided
below.
(i) Delete
subsection (9) and substitute with the following: Power for
master alarms, area
alarms, sensors, and switches from the life safety branch as required in
14.10.4 NMAC.
(ii) Delete subsection (11) and
substitute with the following: Where used
for communications,
wiring from switches or sensors that are supervised or protected as required by
14.10.4 NMAC for life safety and critical branch circuits in which protection
is any of the following types: (a) conduit (b) free air (c) wire (d) cable tray
(e) raceways.
(iii) Delete subsection (14) and
substitute with the following: Provisions
for automatic
restart after a power loss shall be in accordance with 14.10.4 NMAC.
(b) Section 5.1.9.2.3.1 Delete this
section of the NFPA 99 and substitute with the
following: If
communication is achieved by wires, it shall be in accordance with 14.10.4
NMAC.
(3) Section 5.1.10 Category 1
distribution. See this section of
the NFPA 99 except as provided below. Section 5.1.10.11.10 Qualification of
installers. Delete this section of
the NFPA 99 and see 14.6.4 NMAC.
(4) Section 5.1.12 Performance criteria
and testing – category 1 (gases, medical-surgical vacuum, and WAGD). See this section of the NFPA 99 except as
provided below.
(a) Section 5.1.12.3.1.3 Delete
this section of the NFPA 99 and substitute with the following: Inspections
shall be conducted by an inspector certified in accordance with NMAC 14.6.5
NMAC.
(b) Section 5.1.12.3.1.4 Delete
this section of the NFPA 99 and see 14.8.4.9 NMAC.
(c) Section 5.1.12.3.1.5 Delete
this section of the NFPA 99.
(d) Section 5.1.12.4.1.5 Delete
this section of the NFPA 99.
(e) Section 5.1.12.4.1.6 Delete
this section of the NFPA 99.
(5) Section 5.1.13 Category 1 medical
support gases. See this section of
the NFPA 99 except as provided below. Section
5.1.13.3.7.12 Electrical power and control.
See this section of the NFPA 99 except as provided below
(a) Delete subsection (E) and substitute
with the following: Electrical installation and wiring shall conform to the
requirements of 14.10.4 NMAC.
(b) Delete subsection (F) and substitute
with the following: Emergency electrical service for the compressors shall
conform to the requirements of 14.10.4 NMAC.
(6) Section 5.1.14 Category 1 operation
and management. Delete this section
of the NFPA 99.
B. Category 2 Piped Gas and Vacuum Systems. See this section of the NFPA 99.
C. Category 3 Piped Gas and Vacuum Systems. See this section of the NFPA 99 except as
provided below. Section 5.3.3
Sources. See this section of the
NFPA 99 except as provided below.
(1) Section 5.3.3.2.2 Delete this
section of the NFPA 99 and substitute with the following. Emergency electrical service shall conform to
the requirements of 14.10.4 NMAC.
(2) Section 5.3.3.5.11 Oxygen central
supply systems using concentrators.
See this section of the NFPA 99 except delete subsection (3) and
substitute with the following: Emergency electrical service shall conform to
the requirements of 14.10.4 NMAC.
(3) Section 5.3.3.6.1 Medical air
compressor systems. See this section
of the NFPA 99 except delete subsection (3) and substitute with the following:
Emergency electrical service shall conform to the requirements of 14.10.4 NMAC.
(4) Section 5.3.3.7 Medical-surgical
vacuum systems. See this section of
the NFPA 99 except delete subsection (3) and substitute with the following:
Emergency electrical service shall conform to the requirements of 14.10.4 NMAC.
(5) Section 5.3.3.8 Waste anesthetic
gas disposal systems (WAGDs). See
this section of the NFPA 99 except delete subsection (3) and substitute with
the following: Emergency electrical service shall conform to the requirements
of 14.10.4 NMAC.
(6) Section 5.3.3.9 Instrument air
compressor systems. See this section
of the NFPA 99 except delete subsection (3) and substitute with the following: Emergency
electrical service shall conform to the requirements of 14.10.4 NMAC.
[14.8.4.13 NMAC - N,
14.8.4.13 NMAC, 08/01/2026]
14.8.4.14 CHAPTER
6 ELECTRICAL SYSTEMS: Delete this chapter of the NFPA 99 and see 14.10.4
NMAC.
[14.8.4.14 NMAC - N,
14.8.4.14 NMAC, 08/01/2026]
14.8.4.15 CHAPTER
7 INFORMATION TECHNOLOGY AND COMMUNICATIONS SYSTEMS: Delete this chapter of
the NFPA 99 and see 14.10.4 NMAC.
[14.8.4.15 NMAC - N,
14.8.4.15 NMAC, 08/01/2026]
14.8.4.16 CHAPTER
8 PLUMBING: Delete this chapter of the NFPA 99 and see 14.8.2 NMAC.
[14.8.4.16 NMAC - N,
14.8.4.16 NMAC, 08/01/2026]
14.8.4.17 CHAPTER
9 HEATING, VENTILATION, AND AIR CONDITIONING (HVAC): Delete this chapter of
the NFPA 99 and see 14.9.2 NMAC.
[14.8.4.17 NMAC - N,
14.8.4.17 NMAC, 08/01/2026]
14.8.4.18 CHAPTER
10 ELECTRICAL EQUIPMENT: Delete this chapter of the NFPA 99 and see 14.10.4
NMAC.
[14.8.4.18 NMAC - N, 14.8.4.18 NMAC, 08/01/2026]
14.8.4.19 CHAPTER
11 GAS EQUIPMENT: See this chapter of the NFPA 99 except as provided below.
A. Section 11.3 Cylinder and Container Storage
Requirements. See this section of
the NFPA 99 except as provided below.
(1) Section 11.3.5.2 See this
section of the NFPA 99 except as provided below.
(a) Delete subsection (5) and substitute
with the following: If indoors, the room shall be in accordance with 14.7.2
NMAC.
(b) Delete subsection (6) and substitute
with the following: They shall comply with 14.10.4 NMAC for unclassified
(nonhazardous) locations.
(c) Delete subsection (10) and substitute
with the following: They shall be supplied with electrical power compliant with
the requirements of 14.10.4 NMAC.
(2) Section 11.3.6.3 See this
section of the NFPA 99 except delete subsection (2) and substitute with the
following: Minimum distance of 1.5m (5ft) if the entire storage location is
protected by an automatic sprinkler system designed in accordance with 10.25.2
NMAC.
B. Section 11.4 Performance Criteria and Testing. Delete this section of the NFPA 99.
C. Section 11.5 Administration. See this section of the NFPA 99 except as
provided below.
(1) Section 11.5.1 Policies. Delete this section of the NFPA 99.
(2) Section 11.5.2 Gases in cylinders
and liquefied gases in containers. See this section of the NFPA 99 except
as provided below.
(a) Section 11.5.2.1 Qualification and
training of personnel. Delete this
section of the NFPA 99.
(b) Section 11.5.2.2 Transfilling
cylinders. Delete this section of
the NFPA 99.
(c) Section 11.5.2.3 Transfilling
liquid oxygen. See this section of
the NFPA 99.
(d) Section 11.5.2.4 Filling cylinders
from oxygen concentrators. Delete this
section of the NFPA 99.
(e) Section 11.5.2.5 Ambulatory
patients. Delete this section of the
NFPA 99.
(3) Section 11.5.3 Use (including
information and warning signs).
Delete this section of the NFPA 99.
D. Section 11.6 Operation and Management of Cylinders. Delete this section of the NFPA 99.
E. Section 11.7 Liquid Oxygen Equipment. Delete this section of the NFPA 99.
[14.8.4.19 NMAC - N,
14.8.4.19 NMAC, 08/01/2026]
14.8.4.20 CHAPTER
12 EMERGENCY MANAGEMENT: Delete this chapter of the NFPA 99.
[14.8.4.20 NMAC - N,
14.8.4.20 NMAC, 08/01/2026]
14.8.4.21 CHAPTER
13 SECURITY MANAGEMENT: Delete this chapter of the NFPA 99.
[14.8.4.21 NMAC - N,
14.8.4.21 NMAC, 08/01/2026]
14.8.4.22 CHAPTER
14 HYPERBARIC FACILITIES: See this chapter of the NFPA 99 except as
provided below.
A. Section 14.1 Scope. See this section of the NFPA
99.
B. Section 14.2 Construction and Equipment. See this section of the NFPA 99 except as
provided below.
(1) Section 14.2.1 Housing for
hyperbaric facilities. See this
section of the NFPA 99 except as provided below.
(a) Section 14.2.1.1 Delete this
section of the NFPA 99 and see 14.7.2 NMAC.
(b) Section 14.2.1.2 Delete this
section of the NFPA 99 and see 14.7.2 NMAC.
(c) Section 14.2.1.3 Hyperbaric piping
requirements. See this section of
the NFPA 99.
(d) Section 14.2.1.4 Hyperbaric medical
oxygen system requirements. See this
section of the NFPA 99.
(e) Section 14.2.1.5 Hyperbaric medical
air system requirements. See this
section of the NFPA 99.
(f) Section 14.2.1.6 Storage and
handling of medical gases. Delete
this section and substitute with the following: Storage of medical gases. Storage of medical gases shall meet the
applicable requirements of chapter 5.
(2) Section 14.2.2 Fabrication of the
hyperbaric chamber. See this section of the NFPA 99 except as provided
below.
(a) Section 14.2.2.1 See this
section of the NFPA 99 except as provided below.
(i) Section
14.2.2.1.1 Delete this section of the NFPA 99.
(ii) Section 14.2.2.1.2 Delete this
section of the NFPA 99.
(iii) Section 14.2.2.1.3 See this
section of the NFPA 99.
(iv) Section 14.2.2.1.4 See this
section of the NFPA 99.
(b) Section 14.2.2.2 Delete this
section of the NFPA 99.
(c) Section 14.2.2.3 Delete this
section of the NFPA 99.
(d) Section 14.2.2.4 Delete this
section of the NFPA 99.
(e) Section 14.2.2.5 Delete this
section of the NFPA 99 and see 14.7.2 NMAC.
(f) Section 14.2.2.6 Delete this
section of the NFPA 99 and see 14.7.2 NMAC.
(g) Section 14.2.2.7 Delete this
section of the NFPA 99.
(3) Section 14.2.3 Illumination. Delete this section of the NFPA 99.
(4) Section 14.2.4 Chamber ventilation. Delete this section of the NFPA 99.
(5) Section 14.2.5 Emergency
depressurization. Delete this
section of the NFPA 99.
(6) Section 14.2.6 Fire protection in
class A chambers. Delete this
section of the NFPA 99 and see 10.25.5 NMAC.
(7) Section 14.2.7 Pneumatic controls
for class A chambers. Delete this
section of the NFPA 99.
(8) Section 14.2.8 Fire protection in
class B and class C chambers. Delete
this section of the NFPA 99 and see 10.25.2 NMAC.
(9) Section 14.2.9 Electrical systems. Delete this section of the NFPA 99 and see
14.10.4 NMAC.
(10) Section 14.2.10 Communications and
monitoring. Delete this section of
the NFPA 99.
C. Section 14.3 Administration and Maintenance. Delete this section of the NFPA 99.
[14.8.4.22 NMAC - N,
14.8.4.22 NMAC, 08/01/2026]
14.8.4.23 CHAPTER 15 DENTAL GAS AND VACUUM
SYSTEMS: See this chapter of
the NFPA 99 except as provided below.
A. Section 15.1 Applicability. See this section of the NFPA 99.
B. Section 15.2 Nature of Hazards of Gas and Vacuum
Systems. See this section of the
NFPA 99.
C. Section 15.3 Category 1 Dental Gas and Vacuum Systems. See this section of the NFPA 99 except as
provided below. Section 15.3.3.8.4
Operation and management. Delete
this section of the NFPA 99 except see Section 15.3.3.8.4.2 Prohibited
interconnections.
D. Section 15.4 Category 2 Dental Gas and Vacuum Systems. See this section of the NFPA 99 except as
provided below.
(1) Section 15.4.2 Medical gas systems
(oxygen and nitrous oxide). See this
section of the NFPA 99 except as provided below.
(a) Section 15.4.2.1.1 Delete this
section of the NFPA 99 and see 14.6.4 NMAC.
(b) Section 15.4.2.1.2 Delete this
section of the NFPA 99 and see 14.6.4 NMAC.
(c) Section 15.4.2.1.4 Delete this
section of the NFPA 99 and see 14.6.4 NMAC.
(d) Section 15.4.2.4.13 Delete this
section of the NFPA 99 and substitute with the following: Locations containing positive-pressure gases
or cylinders containing oxygen, nitrous oxide, or both shall be separated from
the rest of the building by walls and floors having a 1-hour fire resistive
rating with doors and other opening projective having a ¾-hour fire protection
rating in accordance with 14.7.2 NMAC.
(e) Section 15.4.2.4.15 Delete this
section of the NFPA 99 and see 14.7.2 NMAC.
(2) Section 15.4.9 Operation and
Management. Delete this section of
the NFPA 99 except see Section 15.4.9.2 Prohibited interconnections.
E. Section 15.5 Category 3 Dental and Vacuum Systems. See this section of the NFPA 99 except as
provided below. Section 15.5.8
Operation and management. Delete
this section of the NFPA 99.
[14.8.4.23 NMAC - N,
14.8.4.23 NMAC, 08/01/2026]
14.8.4.24 CHAPTER
16 FEATURES OF FIRE PROTECTION. Delete
this chapter of the NFPA 99 and see 14.7.2 and 10.25.2 NMAC.
[14.8.4.24 NMAC - N,
14.8.4.24 NMAC, 08/01/2026]
History of 14.8.4 NMAC: [RESERVED]